Commissioning & Testing
Every hood’s performance confirmed and documented.
ASHRAE 110 as-installed testing with SF₆ tracer gas, plus dynamic containment verification on each hood, for new labs, renovations and annual programs. More than 40 labs commissioned by the FHC crew.

What we test, hood by hood
ASHRAE 110-2016, as installed (AI)
- Face velocity profile across the opening
- Smoke visualization, local and large volume
- SF₆ tracer gas at left, center and right with a mannequin in the breathing zone, 300 seconds each, logged every second
- Periphery scan and sash movement effect test; VAV response test where the hood has it
- Pass criteria against the project specification
Dynamic containment, the way the lab is used
- A person working at the hood, not a mannequin
- Sash raised and lowered at working speed
- Walk-bys
- Items moved out of the hood
- Lab doors opening
- Various room balance disturbances
- Visible, photographed and recorded.
How a commissioning job runs
- Specification review before bid. We read the spec and flag any issues that may cause repeat tests.
- Pre-test walk with the controls contractor so the hoods run at design setpoint.
- Testing, hood by hood, with the full ASHRAE 110 as-installed procedure and the dynamic challenges above.
- Reports: documented results for each hood, with photos and the dynamic findings.
- Retest of the hoods, after the fix. Hood identification labels.




Case study
Idaho State University, College of Pharmacy
A new teaching lab commissioned with ASHRAE 110 and dynamic verification on every hood. All passed; the lab opened on schedule.
Read the case study
Also for annual programs
If you certify hoods every year, we can run the program, train your in-house people to run it, or help improve your own testing service. Records live in the FHC Performance Tracker, searchable by the hood’s identification label.
Send us the hood schedule
Hood count, types and location gets you a scope and a price.